Development of an optic-electric system for measuring voltage distribution along HVDC converter valves

Zhi Fang, Zhongyuan Zhao, Yuchang Qiu, Jiansheng Wang, Yongming Yu

Research output: Contribution to journalArticlepeer-review

2 Scopus citations

Abstract

An optic-electric measurement system for measuring voltage distribution along the HVDC converter valve, consisting of the transmitter, light route arid receiver, is developed. The system operates on pulse frequency modulation of the signal to be measured. Its bandwidth is from DC to 1.2 MHz, its partial response time is 120 ns and its maximum non-linear error is 1%. Experimental results show that this optic-electric measurement system can meet the requirement of measuring voltage distribution of valve with high capability of suppressing electro-magnetic interference and high measurement precision.

Original languageEnglish
Pages (from-to)69-71
Number of pages3
JournalDianli Xitong Zidonghua/Automation of Electric Power Systems
Volume27
Issue number14
StatePublished - 25 Jul 2003
Externally publishedYes

Keywords

  • Converter valve
  • Optic-electric measurement system
  • Thyristor
  • Voltage distribution

Fingerprint

Dive into the research topics of 'Development of an optic-electric system for measuring voltage distribution along HVDC converter valves'. Together they form a unique fingerprint.

Cite this