Effects of passenger blockage on smoke flow properties in subway station fires

Fan Wu, Yan Wang, Ru Zhou, Juncheng Jiang

科研成果: 期刊稿件文章同行评审

2 引用 (Scopus)

摘要

This study investigates the effects of the passenger blockage on the smoke flow properties in the subway station fires. A series of numerical simulations was conducted in a full-scale subway station model under different smoke exhaust volumes (24–96 m3/s) and passenger blockage scenarios. The parameter uncertainty and the model uncertainty were fully analyzed. Results demonstrate that the optimal smoke exhaust volume is 96 m3/s when there is no passenger blockage. When the passenger blockage exists, its effects on the smoke exhaust efficiency, the smoke layer height, and the temperature profile beneath the ceiling are significant. The optimal smoke exhaust volume can only guarantee the passenger’s safe evacuation in the blockage scenarios with the low passenger blockage level. For the high passenger blockage level, some measures should be taken to reduce the harm to the passengers near the fire source.

源语言英语
期刊Environmental Science and Pollution Research
DOI
出版状态已接受/待刊 - 2022

指纹

探究 'Effects of passenger blockage on smoke flow properties in subway station fires' 的科研主题。它们共同构成独一无二的指纹。

引用此