Experimental investigation and optimization of total energy consumption in humidification-dehumidification system

Xin Huang, Tingfen Ke, Yang Li, Xiang Ling

科研成果: 期刊稿件会议文章同行评审

13 引用 (Scopus)

摘要

In this paper, the electricity consumption model and pressure drop model of humidification-dehumidification (HDH) system is developed. An experimental study is carried out to investigate the effects of operating parameters on the pressure drop of HDH system. The pressure drops in humidifier, dehumidifier and the total pressure drop increase with the increase of air and solution mass flow rate. The values of undetermined coefficient in the pressure drop model are obtained based on the experimental data. Meanwhile, the validation of the pressure drop model is varied though experiment. On this basis, the optimization model for minimum specific total energy consumption (STEC) is proposed. The optimization results show that the value of optimized STEC increase with the increase of evaporation rate requirements. The value of air mass flow rate (mg) should be as small as possible. The adjustment of solution mass flow rate (ml) and solution inlet temperature in humidifier (Tlhi) is a priority. The minimum value of optimized STEC is 822.676 kJ/kg.

源语言英语
页(从-至)3488-3493
页数6
期刊Energy Procedia
158
DOI
出版状态已出版 - 2019
活动10th International Conference on Applied Energy, ICAE 2018 - Hong Kong, 中国
期限: 22 8月 201825 8月 2018

指纹

探究 'Experimental investigation and optimization of total energy consumption in humidification-dehumidification system' 的科研主题。它们共同构成独一无二的指纹。