Investigation and improvement of air distribution system's airflow performance in data centers

Xiaolei Yuan, Jinxiang Liu, Yujiang Yang, Yu Wang, Xiaohang Yuan

科研成果: 期刊稿件会议文章同行评审

12 引用 (Scopus)

摘要

To improve cooling and energy utilization efficiency, under-floor flexible baffles (UFBs) was applied to transform the under-floor airflow pattern in this paper. The application of UFBs impacted the airflow pattern within the Cold aisle containment (CAC). As a result, the exhaust air temperatures of racks were reduced and the exhaust air temperature distribution of the racks was better distributed. The results indicated that, although the use of CAC reduced the exhaust air temperature of racks and the maximum temperature of local hotspot, the air temperature distribution of the racks presented as a non-uniform distribution and the temperature of local hotspot was still high. However, not only could UFBs further reduce exhaust air temperature, but also it made the exhaust airflow more uniform. When the angle between the baffle and CRACs outlet air orientation was at 45, the maximum temperature of local hotspots dropped most, which was from 30.5°C to 28.4°C and achieved a 2.1°C temperature drop. Under the circumstance, the exhaust air temperature distribution was more uniform compared to the data center with CAC but without UFBs.

源语言英语
页(从-至)2895-2902
页数8
期刊Procedia Engineering
205
DOI
出版状态已出版 - 2017
活动10th International Symposium on Heating, Ventilation and Air Conditioning, ISHVAC 2017 - Jinan, 中国
期限: 19 10月 201722 10月 2017

指纹

探究 'Investigation and improvement of air distribution system's airflow performance in data centers' 的科研主题。它们共同构成独一无二的指纹。

引用此