The underfloor air distribution (UFAD) system is widely used in the data center account for the potential of energy saving. However, the uneven distribution of airflow in the underfloor plenum will deteriorate the thermal environment of UFAD system and cause the uniform cooling for servers in the racks. To improve the cooling performance of UFAD system based data center, several kinds of underfloor vertical baffles (UVB) were designed and employed to guide airflow path. By using the computational fluid dynamics (CFD) model, the thermal environment of UFAD based data center had been significantly improved. The results show that the maximum temperature at the top of racks was reduced by about 8.5 °C by deploying the enclosed baffles. The average values of average inlet/outlet temperature were decreased by 4.15 and 3.03 °C, respectively, and the standard deviations of them were 8.8 and 19.3% of those in no-baffle model.

源语言英语
主期刊名Proceedings of the 11th International Symposium on Heating, Ventilation and Air Conditioning, ISHVAC 2019 - Volume 1
主期刊副标题Indoor and Outdoor Environment
编辑Zhaojun Wang, Fang Wang, Peng Wang, Chao Shen, Jing Liu, Yingxin Zhu
出版商Springer
77-85
页数9
ISBN(印刷版)9789811395192
DOI
出版状态已出版 - 2020
活动11th International Symposium on Heating, Ventilation and Air Conditioning, ISHVAC 2019 - Harbin, 中国
期限: 12 7月 201915 7月 2019

出版系列

姓名Environmental Science and Engineering
ISSN(印刷版)1863-5520
ISSN(电子版)1863-5539

会议

会议11th International Symposium on Heating, Ventilation and Air Conditioning, ISHVAC 2019
国家/地区中国
Harbin
时期12/07/1915/07/19

指纹

探究 'Numerical Study on Thermal Management of Data Center Integrated with Underfloor Vertical Baffles' 的科研主题。它们共同构成独一无二的指纹。

引用此