Abstract

A water wall tube of a boiler in a power plant burst. The burst reasons of the water wall tube were analyzed by observing the macroscopic morphology and microstructure of the failed tube, testing the chemical composition and mechanical properties of the tube material, and analyzing the composition of the corrosion products. The results showed that there were obvious corrosion grooves in the burst location, and Na element concentration occurred in local location. The corrosion products were mainly composed of iron oxides (Fe3O4and Fe2O3) and scale, and a certain amount of NaFeO2. There was no obvious plastic deformation in the fracture showing brittle failure characteristic on macro morphology and intergranular cracking characteristic on micro morphology. The microstructure of the burst tube was ferrite and pearlite, and there were a large number of intergranular cracks in the microstructure. During the operation of the boiler, the pH of the boiler water was high (10.0-10.2) for a period of time. Based on the above analysis, it was determined that stress corrosion cracking caused by alkali corrosion was the failure reason of the water wall tube.

Original languageEnglish
Pages (from-to)110-114
Number of pages5
JournalCorrosion and Protection
Volume44
Issue number11
DOIs
StatePublished - 2023

Keywords

  • alkali corrosion
  • stress corrosion cracking
  • tube burst
  • water wall tube

Fingerprint

Dive into the research topics of 'Burst Reasons of Water Wall Tube in Power Plant'. Together they form a unique fingerprint.

Cite this