New estimation of the dosage of scale inhibitor in the cooling water system

Jiang Jiaomei, Xu Yanhua

Research output: Contribution to journalArticlepeer-review

3 Scopus citations

Abstract

In the cooling water system, excessive use of organic phosphate scale inhibitors is harmful to environment. Reducing the dosage of the organic phosphate scale inhibitor is important. A self-made jacketed crystallizer was used in this experiment. The critical pH values have been determined in cooling water systems with series of Ca2+ concentrations by adding different concentration of the scale inhibitor ATMP (Amino Trimethylene Phosphonic Acid) according to the calcium carbonate Metastable zone theory. A model equation at 45 °C and pH=9 was proposed to estimate the lowest dose of the scale inhibitor ATMP. The measured pH value was approximate to the expected pH value in two cooling water systems through verification test.

Original languageEnglish
Pages (from-to)1881-1885
Number of pages5
JournalE-Journal of Chemistry
Volume8
Issue number4
DOIs
StatePublished - Oct 2011

Keywords

  • Critical pH
  • Metastable zone
  • Scale inhibitor dosage

Fingerprint

Dive into the research topics of 'New estimation of the dosage of scale inhibitor in the cooling water system'. Together they form a unique fingerprint.

Cite this